What is the recommended minimum space (envelope) needed around the Klauke tool and jaws to press?

An envelope of 11“ x 7“ is recommended. For 1-3/8“ couplings, a minimum of 4.4” is required between couplings (down to 3.3“ for 1/4“ couplings). A minimum of 2.3“ from the back wall surface is required. You need 2.5“ between couplings for jaws if the tool is coming up from below the fittings to press. …

How do I press onto the flared tubing that comes out of the condenser and evaporator on residential units?

We do not have a specific product designed to press over this type of flared tubing. However, if there is at least 3 inches of straight copper tubing after the flared end is removed, and it is accessible with the jaws, we suggest that you cut the flared end off and press directly to the …

How do I know the correct insertion depth when pushing the RLS fitting onto the copper tube?

Use the depth gauge provided or the Minimum Insertion Depth guidelines below to determine the correct insertion depth. Mark the tubing with a permanent marker to indicate proper insertion depth on every tube. Minimum Insertion Depth 1/4, 5/16, 3/8 Fittings = 1 in / 25.4 mm 1/2, 5/8, 3/4, 7/8, 1, 1-1/8 Fittings = 1-1/4 …

What is a “deep” scratch and how can I remove it?

A deep scratch is defined as one that can be felt with your fingernail. To remove minor scratches try using a new piece of Scotch Brite abrasive pad (maroon color) or 400 grit sandpaper. Alternatively, 180 grit sandpaper/cloth can be used for 15-20 seconds to remove a deep scratch.

What is the most common cause of leaky fittings?

Skipping installation instructions 4 through 8 will cause the tube to leak. It is very important to use the scouring pad and deburring tool. Refrigerant gas running at high pressure is more likely to leak than water at a much lower pressure, therefore, following the tube preparation instructions is critical.